NMD90 Baseboard Heater Cable 300 Volts 90°C Copper

 

 

 

 

Two copper conductors with 90°C XLPE (R90) insulation coloured red and black. Bare bonding wire and overall jacket of moisture resistant and flame retardant PVC, with FT1 rating. Rated 300 volts.
CSA Spec C22.2 No. 48-M90

Applications:

ECS
Catalogue
Number
Conductor

Bonding Wire AWG Size

Insulation
(inches)
Jacket
(inches)

Ampacity

(30°C Ambient)
(amps)

Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
No. AWG
Size
Stranding
NMD14-02-02 2 14 Solid 14 .030 .030 15 .19 x .38 213
NMD12-02-02 2 12 Solid 14 .030 .030 20 .21 x .41 272
NMD10-02-02 2 10 Solid 12 .030 .030 30 .23 x .47 394
NMD08-02-02 2 8 7 Strand 10 .045 .045 45 .33 x .67 696
NMD06-02-02 2 6 7 Strand 8 .045 .045 65 .38 x .81 1,099
NMD04-02-02 2 4 7 Strand 8 .045 .060 85 .770 1,427
NMD03-02-02 2 3 7 Strand 6 .045 .080 105 .860 1,886
NMD02-02-02 2 2 7 Strand 6 .045 .080 120 .930 2,214

 

Note: Sizes 4 AWG and larger are twisted.
Jacket Colour:  Red
Insulation Colours:  Black, Red

 

Applications:

For open or concealed wiring in dry or damp locations where not exposed to mechanical injury.
Minimum recommended installation temperature minus 25°C (with suitable handling procedures).
Maximum conductor temperature 90°C.
Specifically designed for heating circuits.